Enclosure Heat Load Calculations Drive heat: WD = [(HP x 745.7 Watts/HP) / EM] x (1-ED) [Watts] Total heat: Estimate an additional 25%a for wire connections and other components. WT = WD x 1.25a [Watts] Required airflow: CFM = (WT x 3.16) / (Tint - Tamb) [ft.3 / min.] aThis is an estimated factor. Further investigation is necessary to obtain actual total heat dissipated in enclosure.
bUse full-load efficiency. Motor and drive efficiency will vary based on HP and voltage.
aAdditional Heat Loss - This is an estimated factor. Further investigation is necessary to obtain actual total heat dissipated in enclosure.