Home|About Hoffman|Newsroom|Literature|Contact Us|Find A Sales Office|Sales Tools
Product Catalog
Product CatalogServicesIndustry SolutionsHoffman Worldwide
Hoffman
open search box

VARISTAR LHX

VARISTAR LHX is a sealed, self-contained cabinet with an internal air-to-water heat exchanger which uses water to remove heat from the cabinet.     Learn More


DOWNLOADS:

VARISTAR LHX 20 User Manual

BULLETIN:

DPSR

INDUSTRY STANDARDS:

NEMA Type 12
IP 55


Standard Product:

Catalog NumberAxBxCVAC Hz Phase Full Load Amps Max. Cooling Water Inlet Temp. Airflow Max.
m3/hr. 
Rack Units 
Dimension Drawing
Exploded Diagram
Product Diagram
Air Exit Temperature
Usable Cooling Capacity
Cooling Capacity Graph
DV218012LX2
More Info
Add To BOM
2D CAD Drawing
3D STEP Drawing
Spec Sheet
82.68x31.50x47.24in.
2100x800x1200mm
11550/6018.620 kW7-15 C (45-60 F)3,000 (1,766 CFM)42



Technical Data LHX 20:Cooling Capacity

  
Adjustment range air outlet temperature64.4 to 86.0 F (0.2 F increments)


Technical Data LHX 20:Water Circuit

  
Cooling medium1Water
Water inlet temperature242.8 to 59.0 F
Water flow volumeup to 12.36 gal./min.
Static pressure loss in device at 6.8 gal./min.7.5 PSI
Water conduitCopper
Water connection inlet/outletRp 1 in.
Condensate drainRp 1/2 in.

1For optimal operation of the air/water heat exchanger, the water quality requirements must be fulfilled (VDE 3803, please see user manual).

2At a water inlet temperature below 42.8 F and above 59.0 F, the control accuracy cannot be guaranteed. There is also a risk of condensation if the water temperature falls short of the given limits.



Technical Data LHX 20:Air Loop

  
Maximum airflow volume, controlled temperature dependently1765 CFM
Air outlet LHX 20 (adjustable)64.4 to 86.0 F


Technical Data LHX 20:Electrical Data AC

  
Maximum current consumption8.6 A
Maximum power consumption700 W
Apparent power at full load990 VA
Pre-fuse (in the building)10 A


Technical Data LHX 20:Interface

  
ST-bus (RJ 45)Connection possibility for external operation and digital display
RS 232 (SUB-D 9-pin)ASCII protocol, all operational values and status reports, such as temperature, humidity levels, fan operation times
Digital input/output (SUB-D 25-pin)External on/off, alarm outputs and warning signals


Technical Data LHX 20:General Data

General Data  
Cabinet type of protectionIP55, Type 12
Ambient temperature during transport-13 to +158 F
Ambient temperature outside cabinet (during operation)41 to 158 F
Noise level (closed cabinet) at 80 percent fan speed50.7 dB(A)
Relative humidity level5 to 95 percent
Weight of LHX 20 (heat exchanger)173 lbs. (181 lbs. with water)
Weight of LHX 20 with cabinet (approximate)750 lbs.